Project | Traditional requirements | GB51440 new regulations |
---|---|---|
Insulation material | Loose materials are allowed | Plate-shaped/sprayed rigid foam polyurethane is recommended |
Refrigerant charging | No clear recovery requirements | Mandatory recovery of halogenated hydrocarbon refrigerants |
Temperature reduction control | No stage control | Two-stage temperature control: 4℃/-4℃ |
When using polyurethane cyanocondensate material, the moisture content of the base layer must be ≤8%, the brushing interval must be ≥12h, and the overlap width must be ≥80mm.
Ammonia system welds must be 100% radiographically inspected, and the test pressure of the R404A system is increased to 2.9MPa (originally 2.5MPa).
It is recommended to establish a three-dimensional construction simulation mechanism, focusing on monitoring: